ADJUSTING Barometric
Once you have a 2" to 3" fire on the grate, set your
Barometric at .02 - .04. This allowsheated air to remain
in stoker to radiate out into home.
I
!
I
.
TESTING FUME SWITCH
This should be tested twice a season. Place the flame of
a propane torch in the tube of the Fume Switch, inside
back of stove until Fume Switch trips. (Refer to Figure
I-A). If Fume Switch does not trip, shut down the stove,
call your dealer or replace the Fume Switch.
TEMPORARY SHUT DOWN
If your are going away for a week or two, first run
Stoker until Hopper is empty. Vacuum grate and hopper
area. Empty Ash Bucket. Clean PowerVenter Wheel.
Followlighting procedure when you restart. Burn a light
bulb inside stove to prevent moisture.
CAUTION: When shutting down your Stoker Stove,
alwaysdo the following:
1. Shut off stove.
2. Scrape hot coals off grate into Ashpan and remove
from stove to ventilated area.
3. Shut off PowerVenter.
1-8
Resetbutton
Note:Fumeswitchmustberesetaftercoolingif motor
doesnotoperate.Reset,thencheckventingsystem
beforerestartingstove.
END OF THE SEASON NOTES
,..
r
I
~
At the end of the heating season, within a day
of shutting down your stove, clean your stove
and power venter.
Your power Venter should not be left in the wall
during the non-burning season. The Power Venter is
easy to remove from the wall.
STEP 1 Remove the StovePipe from the Stoveand the
Power Venter.
STEP 2 Remove the Trim Collar.
STEP 3 Unplug extension cord from PowerVenter
plug. Place plug in center tube of PowerVenter.
STEP 4 Go outside, remove the 4 screwsthat connect
the Venter head to the Building.
STEP 5 Slowlypull the PowerVente):'outward until
clear of building.
STEP 6 Place Mounting Plate Cover over the outside
of the hole and reattach with the 4 screws.
7